2.Cable Gland for Non-Armoured Cable, DNA Series

Application

The DNA cable glands are suitable for used in zone
1, 2 and zone 21, 22 hazardous areas to enable
direct insertion of normal un-armoured cable into
Ex d equipment or enclosure.

TECHNICAL DATA
Hazardous Area Gas Dust
Zones 1 & 2 21 & 22
Equipment Group/Category
 EX II 2G

 EX II 2D
Symbol of Protection ATEX Ex db eb IIC Gb Ex tb IIIC Db IP66
Symbol of Protection IEC
Certificate  TÜV CY 18 ATEX 0206101 X
T rating Temperature class of enclosure to which will be connected.
Conformity to Standard EN 60079-0:2012+A11:2013, EN 60079-1:2014,
  EN 60079-7:2015, EN 60079-31:2014
 
 
Ambient Temperature -20 oC to +75 oC
Index of Protection IP66
     
SPECIFICATION
Body, gland nut       : Brass (Nickel-plated brass as option)
Thread seal    : Nylon (PA6)

: (For metric threads only)
OPTION
Ordering : Cat. No. (Option) e.g. DNA/S-M1
    (Chromium plated)
CATALOGUE NUMBER AND DIMENSION