8.Empty Enclosures, EJB Series

Application

The EJB junction boxes are designed for use 

  • in hazardous areas,zone 1,2 and
    zone 21, 22

  • provide openings for taps, splices,
    splices or pull box 

  • in indoor or outdoor in damp or wet
    locations or certain corrosive
    environments.

TECHNICAL DATA
Hazardous Area Gas Dust
Zones 1 & 2 21 & 22
Equipment Group/Category II 2G II 2D
Symbol of Protection  Ex d IIB T6/T5 Gb Ex tb IIIC T85/T100 Db IP66
Conformity to Standard EN 60079-0:2012+A11:2013, EN 60079-1:2014,
  EN 60079-31:2014
Ambient Temperature -20 oC to +55 o
Index of Protection IP66
     
Mounting Wall mount
Entries Metric threads 
SPECIFICATION
Body, cover  : Marine grade copper-free aluminium alloy
    with polyester powder coated, RAL 7032 (Grey)
Body, cover          : Marine grade copper-free aluminium 
    alloy with polyester powder coated, 
    RAL 7032 (Grey)
Lid screws     : Stainless steel
Sealing gasket     : Silicone 

 

Electrical Rating    
Rated voltage         : up to 800V.AC. 
(as per equipment specification)
OPTION
CATALOGUE NUMBER AND DIMENSION