9.Control Box, DCT1 Series

Application
The DCT control boxes are designed for use 
■  in hazardous areas, zone 1, 2  and zone 21, 22.
■  installation in petroleum refineries,chemical plants,
    storage areas  where hazardous substances are 
    handled.
■  instrument box with circular or rectangular window.
■  containing analogue and digital measuring  instruments.   
■  indicating the electrical function performed.
 
The circuit breakers are suitable for 
■  short circuit and overcurrent  protection  of service 
    entrance, feeder,branch circuit, lighting or motor circuit
    and serve as  a disconnecting mean.
 
The motor starters are suitable for 
■  single speed, non-reversing starting and   stopping of
    AC squirrel  cage induction motors.
■  direct-on-line or star-delta starting method. 
 
The circuit breaker panelboards are suitable for 
■   control of branch circuit distribution such as lighting 
     circuits, receptacles, pumps or motors.
TECHNICAL DATA
Hazardous Area Gas   Dust
Zones 1 & 2 21&22
Equipment Group/Category Ex II 2G   Ex II 2D
Symbol of Protection Ex d IIB T6/T5 Ex tb IIC T85°C/T100°C Db IP66
Certificate TÜV CY 18 ATEX 0206140 X
Conformity to Standard EN 60079-0:2012+A11:2013, EN 60079-1:2004,
  EN 60079-31:2014
Ambient Temperature -20°C to +55°C
Index of Protection IP66
Entries  NPT  or Metric threads
Mounting  Wall type
Rated Voltage Max. 415v AC 50/60Hz
SPECIFICATION
Body, cover  : Marine grade copper-free aluminium alloy
    with polyester powder coated, RAL 7032 (Grey)
Lid screws  : Stainless steel
Sealing gasket  : Silicone 
OPTION
CATALOGUE NUMBER AND DIMENSION