21.Emergency Light,DMG Series

Application
TECHNICAL DATA
Hazardous Area Gas Dust
Zones 1&2 21 & 22
Equipment Group/Category Ex II 2G Ex II 2D
Symbol of Protection  Ex db  IIB T6 Gb Ex tb IIIC T85 °C Db IP66
Certificate TÜV CY 17 ATEX 0205815  X
Conformity to Standard EN 60079-0:2012+A11:2013, EN 60079-1:2014,
  EN 60079-31:2014, EN 60529 ed 2.2:2013, EN 60598-1:2015
Ambient Temperature oC to+55°C
Index of Protection IP66
   
Entries M25x1.5 or 2-Ø3/4" NPT at right and left side
Mounting  Wall mounting
Connection L,N and E ; for 1-4mm2 cable (Through wiring system with
  an exter terminal block for cable connection at both ends.)
Rated Voltage 220V AC ±5% 50Hz
SPECIFICATION
Body material  : Marine grade copper-free aluminium 
    alloy with polyester powder coated, 
    RAL 7032 (grey)
Lid screws : Stainless steel
Sealing ring    Silicone
     
LED SYSTEM    
Luminous effcient : 100 lm/W
Colour temperature   : 5700 K (Cool White)
Color Rendering Index : >70  
Chip : CREE
Beam angle : Lens of 60° - 90°
     
Electrical for Emergency unit
Operation : Non-maintained mode
Battery : Ni-MH, 7.2V 2.25Ah
Recharge time : 24-hours from fully discharge
Emergency duration : 120 Min. (2-Hours)
OPTION
Option (specify)    
3-hours emergency duration (please specify)
Battery : Ni-MH, 7.2V 4.5Ah
Color Rendering Index(Ra) : >80
CATALOGUE NUMBER AND DIMENSION