1.Fluorescent Lighting Fixture, DNGV Series

Application
TECHNICAL DATA
Hazardous Area Gas   Dust
Zones 1 & 2 21&22
Conforming to ATEX  Ex II 2G   Ex II 2D
Symbol of Protection ATEX Ex db IIB (Ex db IIB Gb) Ex tD A21 (Ex tb IIIC Db)
Symbol of Protection IEC
ATX Certificate PTB 08 ATEX 1018  
IEC Certificate IECEx PTB 08.0014  
Standard ATEX Directive 2014/34/EU, std. EN 60079-0:2006, 
  EN 60079-1:2004, EN61241-0:2006, EN 61241-1:2004
  IECEx Scheme, std. IEC 60079-0:2004,
  IEC 60079-1:2004, iec 61241-0:2004, IEC 61241-1:2004
Ambient Temperature -20  o C to +55  o C   
Index of Protection IP66  
Entries   2-M25x1.5 or 2-Ø3/4” NPT(1-plug)
Mounting  Ceiling or horizontal mounting (standard)
  (Optional mounting provided with 2xM10 eye bolts,
  clamps for, clamps for, Ø2 inch pipe, or bracket)
Connection  L, N and E ; for 1-4mm. 2  cable (socket terminal)
Rated Voltage  220/ 230/ 240V.AC.±5% 50Hz.
SPECIFICATION
Body material  : Body material 
    aluminium alloy with polyester
    powder coated, RAL 7032
    (Grey)
Tube  : Borosilicate glass
Internal reflector  : Stainless steel
Sealing gasket  : Silicone -40 oC to +175 oC
OPTION

 